8–10

Publication 1336 FORCE–5.13 –– September, 1998

Fault text and

code:

Suggested action:

Description:

Fault

type:

Redund Rack Size
34014

Hard

The PLC Communications
Adapter Board has detected
different rack sizes for channels
A and B when RIO with
redundancy was selected.

Check parameters 303 and 304 (DIP
Switch ChA and DIP Switch ChB).
Verify the DIP switch settings. Both
channels must have the same rack size.

Channels A/B LOW

sw5

sw6

1/4 rack

Off

Off

1/2 rack

Off

On

3/4 rack

On

Off

Full rack

On

On

Note: Full racks can only have the
Last/Not Last switch set to Off.

Reset the drive. If the fault persists,
replace the PLC Communications
Adapter Board.

Redund Diff Prot
34015

Hard

The PLC Communications
Adapter Board has detected
redundant operation has been
called for, but channel A is not
configured for the RIO protocol.

Check parameters 303 and 304 (DIP
Switch ChA and DIP Switch ChB).
Verify the DIP switch settings. Both
channels must be configured for the
RIO protocol when using the
redundant mode.

Channel A LOW

sw8

Non–redundant

Off

Redundant

On

Channel B LOW

sw1

sw2

RIO w/o Blk Trans

Off

Off

RIO w/ Blk Trans

Off

On

DH+

On

Off

RIO scanner

On

On

If the fault persists, replace the PLC
Communications Adapter Board.

SW Malfunction
34016

Hard

The integrity check on the board
software has failed.

Reset the drive. If the fault persists,
replace the PLC Communications
Adapter Board.

ChA Dup
Nodeaddr
36019

Soft

The PLC Communications
Adapter Board has detected a
duplicate channel A DH+ node
address.

Check parameter 303 (DIP Switch
ChA) and refer to the table in Chapter
2 to verify the DIP switch settings.

Reset the drive. If the fault persists,
replace the PLC Communications
Adapter Board.