Trend 3 Operator

[Tr3 Operator]

Tr3 Operator specifies the operator used for the
trend trigger evaluation. The available operators
are:

Value

Description

1

Greater Than

(.GT.)

2

Less Than

(.LT.)

3

Equals

(.EQ.)

4

Not Equals

(.NE.)

5

Logical AND

(.AND.)

6

Logical NAND (.NAND.)

7

Logical OR

(.OR.)

8

Logical NOR

(.NOR.)

Parameter Number

477

Parameter Type

Read/Write, Non–Linkable Sink

Display Units / Drive Units

None

Factory Default

5

Minimum Value

1

Maximum Value

8

File – Group

Diagnostics – Trend Setup

478

Trend 3 Sample Rate

[Tr3 Sample Rate]

Tr3 Sample Rate specifies the interval at which the
data in the Trend In 3 parameter is sampled. It is
programmable in 2 millisecond increments. All
values are rounded down to the nearest 2
millisecond interval.

Parameter Number

478

Parameter Type

Read/Write, Non–Linkable Sink

Display Units / Drive Units

Seconds

Factory Default

0.020 Seconds

Minimum Value

0.002 Seconds

Maximum Value

30 Seconds

File – Group

Diagnostics – Trend Setup

479

Trend 3 Post Samples

[Tr3 Post Samples]

Tr3 Post Samples specifies the number of data
samples to be gathered once the trigger evaluation
becomes true. There is always a sample reserved
for the instance when the trigger condition becomes
true.

Parameter Number

479

Parameter Type

Read/Write, Non–Linkable Sink

Display Units / Drive Units

None

Factory Default

15

Minimum Value

0

Maximum Value

499

File – Group

Diagnostics – Trend Setup

480

Trend 3 Continuous Trigger

[Tr3 Cont Trigger]

Tr3 Cont Trigger specifies the type of trend. You can
choose either 0 for one–shot or 1 for continuous.

With a one–shot trend, once the trigger condition is
true and the number of samples after the trigger is
taken are gathered, the trend stops.

With a continuous trend, once the trigger condition is
true and the number of samples after the trigger is
taken are gathered, the trend continues looking for
the next occurrence of a true trigger condition.

Parameter Number

480

Parameter Type

Read/Write, Non–Linkable Sink

Display Units / Drive Units

None

Factory Default

0

Minimum Value

0

Maximum Value

1

File – Group

Diagnostics – Trend Setup