Rockwell Automation 1336T PLC Comm. Adapter, Series B, FRN 2.xx-3.xx User Manual

Page 235

Advertising
background image

8–9

Publication 1336 FORCE–5.13 –– September, 1998

Fault text and

code:

Suggested action:

Description:

Fault

type:

HW Malfunction
34005

Hard

The integrity check on the board
hardware has failed.

Reset the drive. If the fault persists,
replace the PLC Communications
Adapter Board.

ChA Rack Config
34006

Hard

The DIP switch settings indicate
that more than one full rack
should be scanned. This fault is
specific to RIO scanner.

Verify the DIP switch settings for
channel A. RIO scanner can only scan
one full logical rack per channel.

ChB Rack Config
34007

Hard

The DIP switch settings indicate
that more than one full rack
should be scanned. This fault is
specific to RIO scanner.

Verify the DIP switch settings for
channel B. RIO scanner can only scan
one full logical rack per channel.

ChA Module
Group
34012

Hard

The PLC Communications
Adapter Board has detected a
channel A module group that is
not valid for the selected rack
size.

Check parameter 303 (DIP switch
ChA) and verify the DIP switch
settings:

Channel A High

sw3

sw4

Module 0

Off

Off

Module 2

Off

On

Module 4

On

Off

Module 6

On

On

Reset the drive. If the fault persists,
replace the PLC Communications
Adapter Board.

ChB Module
Group
34013

Hard

The PLC Communications
Adapter Board has detected a
channel B module group that is
not valid for the selected rack
size.

Check parameter 304 (DIP switch
ChB) and verify the DIP switch
settings:

Channel B High

sw3

sw4

Module 0

Off

Off

Module 2

Off

On

Module 4

On

Off

Module 6

On

On

Reset the drive. If the fault persists,
replace the PLC Communications
Adapter Board.