Fault queue, Plc block transfer instruction data, Message operation – Rockwell Automation 1336T PLC Comm. Adapter, Series B, FRN 2.xx-3.xx User Manual

Page 166: Example, Trip fault queue number

Advertising
background image

7–20

Publication 1336 FORCE–5.13 –– September, 1998

The Trip Fault Queue Number message provides the fault queue
number of the fault that caused the drive to trip.

PLC Block Transfer Instruction Data

BTW instruction length:

3 words

BTR instruction length:

4 words

Message

3

Header

Word 1

Header

Word 1

PLC Decimal Value

1793

Header

Word 2

Header

Word 3

0

PLC Decimal Value

1793 –– Message OK

Header

Word 2

Header

Word 3

0

-30975 –– Message Error

Header

Word 4

Fault Queue Size

Message Structure

0

PLC Request –– Block Transfer Write

Drive Response –– Block Transfer Read

Message Operation

The Trip Fault Queue Number function provides the entry number of
the fault in the fault queue that tripped the drive The BTR response
contains that number in word 4. The Fault Queue Number is 0 when
the drive is not faulted.

If an error has occurred in the block transfer, word 2 of the response
will be -30975.

Example

In this example, the first entry in the drive fault queue has caused the
drive to trip. Word 4 of the BTR indicates the entry number.

1

0

N10:10

2

3

4

5

6

7

8

9

N10:90

BTW
Data File

BTR
Data File

Data Format

0

0

1

3

0

1794

1794

These values vary depending on parameters and products.

Fault Queue

Trip Fault Queue Number