Message operation, Example, Warning queue read full – Rockwell Automation 1336T PLC Comm. Adapter, Series B, FRN 2.xx-3.xx User Manual

Page 172

Advertising
background image

7–26

Publication 1336 FORCE–5.13 –– September, 1998

Data

Word 15

Clock Time

Date

Day

Data

Word 16

Clock Time

Year

Month

Drive Response –– Block Transfer Read

Message Operation

The Warning Queue Entry Read Full function specified in the BTW
reads the contents of the warning queue specified in word 3 of the
BTW message. The response returns the warning text which can be
shown as ASCII text. The text will have every two characters in
reverse order and return a time stamp indicating the day and time the
warning occurred. The Clock Time is returned in the order shown in
the header message. You should view this information as ASCII text.

This field:

Indicates:

Day

The day of the week, where 1 is Sunday and 7 is
Saturday.

Year

The number of the year. 1990 is referenced as 0.
Therefore, the year 1995 would return a value of 5.

Month

The month of the year, where 1 is January and 12 is
December.

The Date and Time are in hexadecimal format.

Example

In this example, Warning Queue Entry #1 was retrieved from the
drive. The BTR returned the ASCII text Vel Fdbk Loss, with each
two characters reversed. The fault occurred at 10:14am on Thursday
February 23, 1995.

1

0

N10:10

2

3

4

5

6

7

8

9

N10:90

BTW
Data File

BTR
Data File

Data Format

1

1

25942

3

0

2048

2048

8300 25670 27490 19488 29551 8307

N10:100

7681

3594

8224

5048

5893

1282

N10:90

00\01

eV

00\00 08\00

l

df

kb

L

so

s

N10:100

1E\01 0E\0A

00\00 13\B8

17\05 05\02

ASCII Display Values

Warning Queue Read Full