Rockwell Automation 1336T PLC Comm. Adapter, Series B, FRN 2.xx-3.xx User Manual

Page 113

Advertising
background image

6–23

Publication 1336 FORCE–5.13 –– September, 1998

353

Channel A Remote I/O Output 2

[ChA RIOA Out 2]

–– adapter mode

[ChA/B RIOA Out2]

–– adapter mode with redundancy

[ChA RIOS Out 2]

–– scanner mode

ChA RIOx Out 2 contains the third word or data
group to the PLC controller input image table. The
data is transferred to the PLC controller every rack
scan. The PLC Communications Adapter Board can
provide this value directly. Other drive functions can
provide this value through a configuration link.

Parameter Number

353➀

Parameter Type

Read/Write, Sink

Display Units / Drive Units

None

Factory Default

None

Minimum Value

–32767

Maximum Value

+32767

File – Group

Communications I/O – Channel A

➀ This parameter is not available if you set up channel A for DH+. Availability also
depends on the selected rack size.

Note: All eight words are displayed regardless of the rack size. Only the number of words corresponding to the rack size and protocol
(with or without block transfer) are functional.

354

Channel A Remote I/O Output 3

[ChA RIOA Out 3]

–– adapter mode

[ChA/B RIOA Out3]

–– adapter mode with redundancy

[ChA RIOS Out 3]

–– scanner mode

ChA RIOx Out 3 contains the fourth word or data
group to the PLC controller input image table. The
data is transferred to the PLC controller every rack
scan. The PLC Communications Adapter Board can
provide this value directly. Other drive functions can
provide this value through a configuration link.

Parameter Number

354➀

Parameter Type

Read/Write, Sink

Display Units / Drive Units

None

Factory Default

None

Minimum Value

–32767

Maximum Value

+32767

File – Group

Communications I/O – Channel A

➀ This parameter is not available if you set up channel A for DH+. Availability also
depends on the selected rack size.

Note: All eight words are displayed regardless of the rack size. Only the number of words corresponding to the rack size and protocol
(with or without block transfer) are functional.

355

Channel A Remote I/O Output 4

[ChA RIOA Out 4]

–– adapter mode

[ChA/B RIOA Out4]

–– adapter mode with redundancy

[ChA RIOS Out 4]

–– scanner mode

ChA RIOx Out 4 contains the fifth word or data
group to the PLC controller input image table. The
data is transferred to the PLC controller every rack
scan. The PLC Communications Adapter Board can
provide this value directly. Other drive functions can
provide this value through a configuration link.

Parameter Number

355➀

Parameter Type

Read/Write, Sink

Display Units / Drive Units

None

Factory Default

None

Minimum Value

–32767

Maximum Value

+32767

File – Group

Communications I/O – Channel A

➀ This parameter is not available if you set up channel A for DH+. Availability also
depends on the selected rack size.

Note: All eight words are displayed regardless of the rack size. Only the number of words corresponding to the rack size and protocol
(with or without block transfer) are functional.