1–9

Publication 1336 FORCE–5.13 –– September, 1998

When configured for RIO adapter communications, the PLC
Communications Adapter Board can:

Support 57.6K, 115K, or 230K baud communication rates at all
valid module groups.

Be configured as a 1/4, 1/2, 3/4, or full I/O rack.

Be configured to ignore PLC fault conditions and continue
operating.

Support transfer of multiple drive parameter read or writes in a
single block transfer.

Allow the 1336 FORCE to be connected to two PLCs in a
master/backup configuration (which is referred to as redundant
mode) where drive control can be switched between two PLCs
and specifies which PLC is currently in control.

Allow the block transfer feature to be disabled via a DIP switch
setting and provide an extra word of discrete data.

The terminating resistors (R1 and R2 in the figure below) depend on
the baud rate:

If you are using this baud rate:

Then, you need to use this

terminating resistor:

57.6K

150 Ohm

115K

150 Ohm

230K

82 Ohm

The following is the wiring configuration necessary for RIO adapter:

PLC Communications

Adapter Board

Channel A or B

1
Shield
2

PLC Communications

Adapter Board

Channel A or B

1
Shield
2

PLC Communications

Adapter Board

Channel A or B

1
Shield
2

Blue

Shield

Clear

Blue

Shield

Clear

PLC Controller

Blue

Shield

Clear

R1

R2

Blue Hose

Blue Hose

Blue Hose