The Run Time Accumulator Data Read message provides the drive
with the accumulated time for running services. This information is
in hours and is read only. This function is typically used as a
maintenance feature.

PLC Block Transfer Instruction Data

BTW instruction length:

3 words

BTR instruction length:

4 words

Header

Word 1

Header

Word 1

Header

Word 2

Header

Word 2

Data

Word 3

0

Message Structure

Header

Word 3

0

PLC Decimal Value

2817

PLC Decimal Value

2817 –– Message OK

-29951 –– Message Error

Message Length

3

Data

Word 4

Accumulated Value in

Hours

0

PLC Request –– Block Transfer Write

Drive Response –– Block Transfer Read

Message Operation

The Run Time Accumulator Data Read through BTR word 4,
provides the running service time in hours. As a maintenance feature,
you can use this information to help define a service schedule for the
drive.

You can clear the accumulated time through a Clear Run Time
Accumulator request. Information can then provide the accumulated
run time between each scheduled service.

Run Time Accumulator

Run Time Accumulator Data