Rockwell Automation 1336T PLC Comm. Adapter, Series B, FRN 2.xx-3.xx User Manual
Page 53

3–9
Publication 1336 FORCE–5.13 –– September, 1998
Rung 1
01
B3
( )
Start
1
0:21
bit 1
Par 367
(
)
Start
02
B3
( )
Stop
0
0:21
bit 8
Par 367
(
)
Stop
Rung 2
03
B3
Rung 3
03
B3
( )
Current Limit Stop
11
0:21
bit 9
Par 367
(
)
Ramp
01
B3
Speed Reference Select
bit 12
Par 367
(
)
Rung 4
Disabled
05
B3
06
B3
07
B3
( )
14
0:21
bit 13
Par 367
(
)
( )
15
0:21
bit 14
Par 367
(
)
( )
16
0:21
Speed Ref
Select A
Speed Ref
Select B
Speed Ref
Select C
Rung 5
04
B3
( )
Fault Reset
3
0:21
bit 3
Par 367
(
)
Rung 6
01
B3
Run Speed Reference
Clear Fault
MOV
MOVE
SOURCE
DEST
N10:01
0:22
In this example, word 1 of integer file N10 stores the speed reference
for the drive. The MOV block in rung 6 of the example PLC
program transfers the 16 bit word N10:01 to word 2 of the output
image table. Because word 2 of the output image table is sent to
parameter 332, which in turn is linked to parameter 101, the 16–bit
word N10:01 is the speed reference input to drive parameter 101.