Rockwell Automation 1336T PLC Comm. Adapter, Series B, FRN 2.xx-3.xx User Manual

Page 241

Advertising
background image

8–15

Publication 1336 FORCE–5.13 –– September, 1998

Fault text and

code:

Suggested action:

Description:

Fault

type:

ChA G0 Rack Flt
36027

Soft,
warning,
or none

The DIP switches indicate that a
rack should be scanned at
module group 0, but no rack is
being scanned at that module
group.

Check cables for connections.

Check if the rack is inhibited.

Check if power is applied to the RIO
adapter channel.

ChA G2 Rack Flt
36028

Soft,
warning,
or none

The DIP switches indicate that a
rack should be scanned at
module group 2, but no rack is
being scanned at that module
group.

Check cables for connections.

Check if the rack is inhibited.

Check if power is applied to the RIO
adapter channel.

ChA G4 Rack Flt
36029

Soft,
warning,
or none

The DIP switches indicate that a
rack should be scanned at
module group 4, but no rack is
being scanned at that module
group.

Check cables for connections.

Check if the rack is inhibited.

Check if power is applied to the RIO
adapter channel.

ChA G6 Rack Flt
36030

Soft,
warning,
or none

The DIP switches indicate that a
rack should be scanned at
module group 6, but no rack is
being scanned at that module
group.

Check cables for connections.

Check if the rack is inhibited.

Check if power is applied to the RIO
adapter channel.

ChB G0 Rack Flt
36031

Soft,
warning,
or none

The DIP switches indicate that a
rack should be scanned at
module group 0, but no rack is
being scanned at that module
group.

Check cables for connections.

Check if the rack is inhibited.

Check if power is applied to the RIO
adapter channel.

ChB G2 Rack Flt
36032

Soft,
warning,
or none

The DIP switches indicate that a
rack should be scanned at
module group 2, but no rack is
being scanned at that module
group.

Check cables for connections.

Check if the rack is inhibited.

Check if power is applied to the RIO
adapter channel.

ChB G4 Rack Flt
36033

Soft,
warning,
or none

The DIP switches indicate that a
rack should be scanned at
module group 4, but no rack is
being scanned at that module
group.

Check cables for connections.

Check if the rack is inhibited.

Check if power is applied to the RIO
adapter channel.

ChB G6 Rack Flt
36034

Soft,
warning,
or none

The DIP switches indicate that a
rack should be scanned at
module group 6, but no rack is
being scanned at that module
group.

Check cables for connections.

Check if the rack is inhibited.

Check if power is applied to the RIO
adapter channel.