Clock data, Plc block transfer instruction data, Message operation – Rockwell Automation 1336T PLC Comm. Adapter, Series B, FRN 2.xx-3.xx User Manual

Page 190: Real time clock data read

Advertising
background image

7–44

Publication 1336 FORCE–5.13 –– September, 1998

The Real Time Clock Data Read message is provided to allow the
drive to read the specified real–time clock. The slave device can
read the time in seconds, minutes, and hours as well as the day, date,
month, and year.

PLC Block Transfer Instruction Data

BTW instruction length:

3 words

BTR instruction length:

7 words

Header

Word 1

Header

Word 1

Header

Word 2

Header

Word 2

Header

Word 3

0

Message Structure

Message Length

3

Header

Word 3

0

PLC Decimal Value

2816

Clock Time

Seconds

Clock Time

Hour

Minute

PLC Decimal Value

2816 –– Message OK

-29952 –– Message Error

Clock Time

Date

Day

Clock Time

Year

Month

Data

Word 4

Data

Word 5

Data

Word 6

Data

Word 7

0

PLC Request –– Block Transfer Write

10ths of MS

Drive Response –– Block Transfer Read

Message Operation

The Real Time Clock Data Read function reads the real–time clock
data from the drive. The Clock Time is returned in the order shown
in the header message. You should view this information as ASCII
text.

The Time is based on a 24–hour clock.

Clock Data

Real Time Clock Data Read

Advertising