Trend file, Plc block transfer instruction data, All info – Rockwell Automation 1336T PLC Comm. Adapter, Series B, FRN 2.xx-3.xx User Manual
Page 211

7–65
Publication 1336 FORCE–5.13 –– September, 1998
The All Info function allows you to read the set up information for a
trend file in a single message instead of reading the individual
parameters within the drive.
PLC Block Transfer Instruction Data
BTW instruction length:
3 words
BTR instruction length:
15 words
Header
Word 1
Header
Word 1
Header
Word 2
Header
Word 2
Header
Word 3
Trend Number
Message Structure
Header
Word 3
Trend Number
PLC Decimal Value
4098
PLC Decimal Value
4098 –– Message OK
–28670 –– Message Error
Message Length
3
Message Length
15
PLC Request –– Block Transfer Write
Drive Response –– Block Transfer Read
Data
Word 4
Trend Status
Data
Word 5
Trend Sample Size
Data
Word 6
Post Samples
Data
Word 7
Operator Data
Data
Word 8
Sample Time Rate
Data
Word 9
Mode
Data
Word 10
Comparison A Value
Data
Word 11
Comparison A Link
Data
Word 12
Comparison B Value
Data
Word 13
Comparison B Link
Data
Word 14
Sampling Input Parameter
Data
Word 15
Trend Output Parameter
Trend File
All Info