Rockwell Automation 1336T PLC Comm. Adapter, Series B, FRN 2.xx-3.xx User Manual

Page 233

Advertising
background image

8–7

Publication 1336 FORCE–5.13 –– September, 1998

Fault text and

code:

Suggested action:

Description:

Fault

type:

Drv Types Differ
24010

Soft

There is a discrepancy between
the drive type on the base driver
board and the parameter 220
and 221 values in BRAM.

Reset the drive. If the fault persists:

1. Execute a BRAM recall.

2. Execute a BRAM store.

3. Reset the drive.

4. Clear the faults.

When you are done with these steps,
verify all parameter values.

I11 Drive Type
24011

Hard

The drive type code in Serial E2
on the base driver board is not a
valid code per the language
module table.

Replace the base driver board.

Main BRAM
Cksm
24012

Soft

There is a discrepancy between
the calculated checksum and the
saved checksum for the main
control board.

Reset the drive. If the fault persists:

1. Execute a BRAM recall.

2. Execute a BRAM store.

3. Reset the drive.

4. Clear the faults.

When you are done with these steps,
verify all parameter values.

SW Malfunction
24013

Hard

The integrity check on the board
software has failed.

Reset the drive. If the fault persists,
you may have to replace either the
PLC Communications Adapter Board
or the main control board.

SW Malfunction
24014

Hard

The integrity check on the board
software has failed.

Reset the drive. If the fault persists,
you may have to replace either the
PLC Communications Adapter Board
or the main control board.

SW Malfunction
24015

Hard

The integrity check on the board
software has failed.

Reset the drive. If the fault persists,
replace the PLC Communications
Adapter Board.

SW Malfunction
24016

Hard

The integrity check on the board
software has failed.

Reset the drive. If the fault persists,
replace the PLC Communications
Adapter Board.

SW Malfunction
24017

Hard

The integrity check on the board
software has failed.

Reset the drive. If the fault persists,
replace the PLC Communications
Adapter Board.

SW Malfunction
24018

Hard

The integrity check on the board
software has failed.

Reset the drive. If the fault persists,
replace the PLC Communications
Adapter Board.

AP SW/LM Rev
Err
24025

Soft

There is a PLC
Communications Adapter Board
software/language module
mismatch.

Verify the board software and language
module versions with Allen–Bradley.