Rockwell Automation 1336T PLC Comm. Adapter, Series B, FRN 2.xx-3.xx User Manual

Page 234

Advertising
background image

8–8

Publication 1336 FORCE–5.13 –– September, 1998

Fault text and

code:

Suggested action:

Description:

Fault

type:

Adapter Config
Err
24026

Soft

The PLC Communications
Adapter Board has detected that
board DIP switch settings do
not match values stored in
BRAM.

Verify the DIP switch settings and
execute a BRAM store to save the new
settings.

No AP LM Exists
25023

Hard

The PLC Communications
Adapter Board has detected that
a language module has not been
installed on the PLC
Communications Adapter
Board.

Reset the drive. If the fault persists,
replace the language module.

SP Pt1 Timeout
26038

Soft,
warning,
or none

The device connected to Port 1
of SCANport has been
disconnected.

None

SP Pt2 Timeout
26039

Soft,
warning,
or none

The device connected to Port 2
of SCANport has been
disconnected.

None

SP Pt3 Timeout
26040

Soft,
warning,
or none

The device connected to Port 3
of SCANport has been
disconnected.

None

SP Pt4 Timeout
26041

Soft,
warning,
or none

The device connected to Port 4
of SCANport has been
disconnected.

None

SP Pt5 Timeout
26042

Soft,
warning,
or none

The device connected to Port 5
of SCANport has been
disconnected.

None

SP Comm Fault
26043

Hard

The integrity check on the board
hardware has failed.

Reset the drive. If the fault persists,
replace the PLC Communications
Adapter Board.

SP Offline
26057

Soft,
warning,
or none

Excessive Communication
errors.

Check SCANport connection/cables.
Replace terminal. If fault persists,
replace PLC. Comm Adapter Brd.

HW Malfunction
34001

Hard

The integrity check on the board
hardware has failed.

Reset the drive. If the fault persists,
replace the PLC Communications
Adapter Board.

HW Malfunction
34002

Hard

The integrity check on the board
hardware has failed.

Reset the drive. If the fault persists,
replace the PLC Communications
Adapter Board.

HW Malfunction
34003

Hard

The integrity check on the board
hardware has failed.

Reset the drive. If the fault persists,
replace the PLC Communications
Adapter Board.

HW Malfunction
34004

Hard

The integrity check on the board
hardware has failed.

Reset the drive. If the fault persists,
replace the PLC Communications
Adapter Board.