DH+ Configuration

When you configure a communications channel for DH+
communications, the PLC Communications Adapter Board becomes
a station on the DH+ link. You can pass information to and from the
drive using the DH+ protocol.

When configured for DH+ communications, the PLC
Communications Adapter Board can:

Support 57.6K, 115K, or 230K baud communication rates.

Support read or write messages for blocks of parameters.

Allow the PLC to to issue 1336 FORCE messages using a method
similar to RIO block transfer.

The terminating resistors (R1 and R2 in the figure below) depend on
the baud rate:

If you are using this baud rate:

Then, you need to use this

terminating resistor:

57.6K

150 Ohm

115K

150 Ohm

230K

82 Ohm

The following is the wiring configuration necessary for DH+:

PLC Communications

Adapter Board

Channel A or B

1
Shield
2

PLC Communications

Adapter Board

Channel A or B

1
Shield
2

PLC Communications

Adapter Board

Channel A or B

1
Shield
2

Clear

Shield

Blue

Clear

Shield

Blue

PLC Controller

Clear

Shield

Blue

R1

R2

Blue Hose

Blue Hose

Blue Hose