Dh+ configuration – Rockwell Automation 1336T PLC Comm. Adapter, Series B, FRN 2.xx-3.xx User Manual
Page 27

1–11
Publication 1336 FORCE–5.13 –– September, 1998
DH+ Configuration
When you configure a communications channel for DH+
communications, the PLC Communications Adapter Board becomes
a station on the DH+ link. You can pass information to and from the
drive using the DH+ protocol.
When configured for DH+ communications, the PLC
Communications Adapter Board can:
•
Support 57.6K, 115K, or 230K baud communication rates.
•
Support read or write messages for blocks of parameters.
•
Allow the PLC to to issue 1336 FORCE messages using a method
similar to RIO block transfer.
The terminating resistors (R1 and R2 in the figure below) depend on
the baud rate:
If you are using this baud rate:
Then, you need to use this
terminating resistor:
57.6K
150 Ohm
115K
150 Ohm
230K
82 Ohm
The following is the wiring configuration necessary for DH+:
PLC Communications
Adapter Board
Channel A or B
1
Shield
2
PLC Communications
Adapter Board
Channel A or B
1
Shield
2
PLC Communications
Adapter Board
Channel A or B
1
Shield
2
Clear
Shield
Blue
Clear
Shield
Blue
PLC Controller
Clear
Shield
Blue
R1
R2
Blue Hose
Blue Hose
Blue Hose