For the meter to indicate speed in both directions, you need to adjust
the scale and offset parameters as shown in Figure 2–3. Working in
the opposite direction as the analog inputs, apply the scale factor
first. The drive sends a

±

4096 digital value to indicate

±

100%

velocity feedback for a total digital range of 8192. The meter,
having an analog range of 0 through 10V

dc, requires a digital range

of 2048. This is done by applying a scale factor of 0.25 (8192

×

0.25

= 2048).

To have the 0 through 10V

dc meter indicate

±

100% feedback, you

need to apply an offset. Offset parameters for analog outputs will
again add the corresponding digital value to the range. In this case,
an offset of 5 volts adds a digital value of 1024 to the range. This
allows full range deflection on the 0 to 10 volt meter, with 5 volts
indicating zero speed.

Figure 2.3
Analog Output 1 +100% Speed Indication

–100%

Base Speed

0 Speed

+100%

Base Speed

5V

0V

10V

+4096 (+100% SPEED)

0

–4096 (–100% SPEED)

+1024

0

–1024

+2048
+1024

0

+10V = + 100% Base Speed

+5V = 0 Speed

Scale

Par 401

X 0.25

Offset

Par 400

5V = 1024

D

A

Digital Range

From Drive

Scaled by 0.25

0V = –100%

Offset by 5V, Adding 1024

Digital Value

Meter Voltage

% Base Speed

– 4096

– 1024
+ 1024

0

0 Volts

– 100%

0

0

+ 1024

0

5 Volts

0%

4096

+ 1024
+ 1024

2048

10 Volts

+ 100%

(+ 2048 = + 10V)

Par 269

Par 387

Velocity

Analog Out 1

Feedback