6–46

Publication 1336 FORCE–5.13 –– September, 1998

442

SCANport Fault Status

[SP Fault Sts]

SP Fault Sts indicates which communications soft
faults the drive has encountered at the ports.

Parameter Number

442

Parameter Type

Read Only, Source

Display Units / Drive Units

Bits

Factory Default

0011

1110

Minimum Value

0000

0000

Maximum Value

0011

1110

File – Group

Diagnostics – Fault Select/Status

Communications I/O – Fault Select/Status

Enums
Bit 5 Bit 4 Bit 3 Bit 2 Bit 1

Enums

Fault

Port 1

SP Pt1 Timeout (Flt 26038)

Port 2

SP Pt2 Timeout (Flt 26039)

Port 3

SP Pt3 Timeout (Flt 26040)

Port 4

SP Pt4 Timeout (Flt 26041)

Port 5

SP Pt5 Timeout (Flt 26042)

443

SCANport Warning Status

[SP Warn Sts]

SP Warn Sts indicates which communications
warnings the drive has encountered at the ports.

Parameter Number

443

Parameter Type

Read Only, Source

Display Units / Drive Units

Bits

Factory Default

0011

1110

Minimum Value

0000

0000

Maximum Value

0011

1110

File – Group

Diagnostics – Fault Select/Status

Communications I/O – Fault Select/Status

Enums
Bit 5 Bit 4 Bit 3 Bit 2 Bit 1

Enums

Warning

Port 1

SP Pt1 Timeout (Flt 26038)

Port 2

SP Pt2 Timeout (Flt 26039)

Port 3

SP Pt3 Timeout (Flt 26040)

Port 4

SP Pt4 Timeout (Flt 26041)

Port 5

SP Pt5 Timeout (Flt 26042)

454

Trend Input 1

[Trend In 1]

Trend In 1 specifies the data value to sample at the
specified trend sample rate. You should link Trend
In 1 to a source parameter (such as velocity, torque,
or current) for the trend to make sense.

Parameter Number

454

Parameter Type

Read/Write, Sink

Display Units / Drive Units

Dependent on Link➀

Factory Default

0

Minimum Value

–32767➀

Maximum Value

+32767➀

File – Group

Diagnostics – Trend I/O

➀ These values depend on the source parameter that this parameter is linked to.
For example, if the source parameter’s drive units are rpm, then Trend In 1’s drive
units will be displayed in rpm. The minimum and maximum values are also link
dependent.

455

Trend 1 Operand Parameter X

[Tr1 Opnd Parm X]

Tr1 Opnd Parm X specifies the first of two parameter
numbers for the trend trigger evaluation. The data
value for the entered link parameter number is used
in the trigger evaluation.

Parameter Number

455

Parameter Type

Read/Write, Sink

Display Units / Drive Units

Dependent on Link➀

Factory Default

0

Minimum Value

–32767➀

Maximum Value

+32767➀

File – Group

Diagnostics – Trend Setup

➀ These values depend on the source parameter that this parameter is linked to.
For example, if the source parameter’s drive units are rpm, then Tr1 Opnd Parm X’s
drive units will be displayed in rpm. The minimum and maximum values are also
link dependent.