Analog Input 2 Scale

[Analog In 2 Scale]

Analog In 2 Scale determines the scale factor or
gain for the Analog In 2 value. A +10V dc signal
applied to Analog In 2 at TB21 is converted to a
+2048 digital value used by the 1336 FORCE.
Before the digital value is displayed or transferred to
the drive, the scale factor is applied allowing an
effective digital range of

±

32767 (16 x 2048). The

absolute digital value is clamped at 32767.

Scale Factor

Drive Units

1

2048

2

4096

4

8192

16

32767

Parameter Number

395

Parameter Type

Read/Write, Non–Linkable Sink

Display Units / Drive Units

±

32767

Factory Default

+1

Minimum Value

–16

Maximum Value

+16

File – Group

Communications I/O – Analog Input

396

Analog Input 3 Offset

[Analog In 3 Offset]

Analog In 3 Offset determines the offset applied to
the raw Analog In 3 values before the scale factor is
applied. This allows you to shift the range of the
analog input.

Parameter Number

396

Parameter Type

Read/Write, Non–Linkable Sink

Display Units / Drive Units

±

4096

Factory Default

0

Minimum Value

–20 Volts

Maximum Value

+20 Volts

File – Group

Communications I/O – Analog Input

397

Analog Input 3 Scale

[Analog In 3 Scale]

Analog In 3 Scale determines the scale factor or
gain for the Analog In 3 value. A +10V dc signal
applied to Analog In 3 at TB21 is converted to a
+2048 digital value used by the 1336 FORCE.
Before the digital value is displayed or transferred to
the drive, the scale factor is applied allowing an
effective digital range of

±

32767 (16 x 2048). The

absolute digital value is clamped at 32767.

Scale Factor

Drive Units

1

2048

2

4096

4

8192

16

32767

Parameter Number

397

Parameter Type

Read/Write, Non–Linkable Sink

Display Units / Drive Units

±

32767

Factory Default

+1

Minimum Value

–16

Maximum Value

+16

File – Group

Communications I/O – Analog Input

398

Analog Input 4 Offset

[Analog In 4 Offset]

Analog In 4 Offset determines the offset applied to
the raw Analog In 4 values before the scale factor is
applied. This allows you to shift the range of the
analog input.

Parameter Number

398

Parameter Type

Read/Write, Non–Linkable Sink

Display Units / Drive Units

±

4096

Factory Default

0

Minimum Value

–20 Volts

Maximum Value

+20 Volts

File – Group

Communications I/O – Analog Input