background image

6–36

Publication 1336 FORCE–5.13 –– September, 1998

411

Jog Mask

[Jog Mask]

Jog Mask controls which ports can issue a jog
command.

Parameter Number

411

Parameter Type

Read/Write, Non–Linkable Sink

Display Units / Drive Units

Bits

Factory Default

0

Minimum Value

0

Maximum Value

0FE Hex

File – Group

Communications I/O – SCANport Masks

Enums

Bit 1 = Port 1

Bit 2 = Port 2

Bit 3 = Port 3

Bit 4 = Port 4

Bit 5 = Port 5

Bit 6 = Channel A Bit 7 = Channel B

412

Reference Mask

[Ref Mask]

Ref Mask controls which ports can select an
alternate reference or preset speed.

Parameter Number

412

Parameter Type

Read/Write, Non–Linkable Sink

Display Units / Drive Units

Bits

Factory Default

0

Minimum Value

0

Maximum Value

0FE Hex

File – Group

Communication I/O – SCANport Masks

Enums

Bit 1 = Port 1

Bit 2 = Port 2

Bit 3 = Port 3

Bit 4 = Port 4

Bit 5 = Port 5

Bit 6 = Channel A Bit 7 = Channel B

413

Clear Fault Mask

[Clr Fault Mask]

Clr Fault Mask controls which ports can generate a
clear fault command.

Parameter Number

413

Parameter Type

Read/Write, Non–Linkable Sink

Display Units / Drive Units

Bits

Factory Default

0

Minimum Value

0

Maximum Value

0FE Hex

File – Group

Communications I/O – SCANport Masks

Enums

Bit 1 = Port 1

Bit 2 = Port 2

Bit 3 = Port 3

Bit 4 = Port 4

Bit 5 = Port 5

Bit 6 = Channel A Bit 7 = Channel B

414

Reset Drive Mask

[Reset Drive Mask]

Reset Drive Mask controls which ports can reset a
fault.

Parameter Number

414

Parameter Type

Read/Write, Non–Linkable Sink

Display Units / Drive Units

Bits

Factory Default

0

Minimum Value

0

Maximum Value

0FE Hex

File – Group

Communication I/O – SCANport Masks

Enums

Bit 1 = Port 1

Bit 2 = Port 2

Bit 3 = Port 3

Bit 4 = Port 4

Bit 5 = Port 5

Bit 6 = Channel A Bit 7 = Channel B

415

Local Mask

[Local Mask]

Local Mask controls which ports are allowed to take
exclusive control of drive logic commands except
Stop. (Stop is accepted from any device regardless
of who has control.) You can only take exclusive
local control while the drive is stopped.

Parameter Number

415

Parameter Type

Read/Write, Non–Linkable Sink

Display Units / Drive Units

Bits

Factory Default

0

Minimum Value

0

Maximum Value

0FE Hex

File – Group Communications I/O – SCANport Owners

Enums

Bit 1 = Port 1

Bit 2 = Port 2

Bit 3 = Port 3

Bit 4 = Port 4

Bit 5 = Port 5

Bit 6 = Channel A Bit 7 = Channel B

Advertising