background image

6–30

Publication 1336 FORCE–5.13 –– September, 1998

386

SCANport Analog Output

[SP Analog Out]

SP Analog Out passes the value it contains to the
attached SCANport devices. For example, you can
link one of the output parameters to SP Analog Out
and each of the five SCANport devices could read
the value of the output parameter.

Parameter Number

386

Parameter Type

Read/Write, Sink

Display Units / Drive Units

±

32767

Factory Default

0

Minimum Value

–32767

Maximum Value

+32767

File – Group

Communications I/O – Analog Output

387

Analog Output 1

[Analog Out 1]

Analog Out 1 converts a

±

32767 value to a

±

10V

signal. The digital value is linked to a 1336 FORCE
source parameter which provides a value that is
scaled and offset. The results are converted to a
voltage signal, where

±

2048 results in a

±

10V

output.

Parameter Number

387

Parameter Type

Read/Write, Sink

Display Units / Drive Units

±

32767

Factory Default

0

Minimum Value

–32767

Maximum Value

+32767

File – Group

Communication I/O – Analog Output

388

Analog Output 2

[Analog Out 2]

Analog Out 2 converts a

±

32767 value to a

±

10V

signal. The digital value is linked to a 1336 FORCE
source parameter which provides a value that is
scaled and offset. The results are converted to a
voltage signal, where

±

2048 results in a

±

10V

output.

Parameter Number

388

Parameter Type

Read/Write, Sink

Display Units / Drive Units

±

32767

Factory Default

0

Minimum Value

–32767

Maximum Value

+32767

File – Group

Communication I/O – Analog Output

389

Analog Output 3

[Analog Out 3]

Analog Out 3 converts a

±

32767 value to a

±

10V

signal. The digital value is linked to a 1336 FORCE
source parameter which provides a value that is
scaled and offset. The results are converted to a
voltage signal, where

±

2048 results in a

±

10V

output.

Parameter Number

389

Parameter Type

Read/Write, Sink

Display Units / Drive Units

±

32767

Factory Default

0

Minimum Value

–32767

Maximum Value

+32767

File – Group

Communication I/O – Analog Output

390

Analog Output 4

[Analog Out 4]

Analog Out 4 converts a

±

32767 value to a

±

10V

signal. The digital value is linked to a 1336 FORCE
source parameter which provides a value that is
scaled and offset. The results are converted to a
voltage signal, where

±

2048 results in a

±

10V

output.

Parameter Number

390

Parameter Type

Read/Write, Sink

Display Units / Drive Units

±

32767

Factory Default

0

Minimum Value

–32767

Maximum Value

+32767

File – Group

Communication I/O – Analog Output