Parameter read – Rockwell Automation 1336T PLC Comm. Adapter, Series B, FRN 2.xx-3.xx User Manual

Page 150

Advertising
background image

7–4

Publication 1336 FORCE–5.13 –– September, 1998

This message is sent by the PLC Communications Adapter Board
and reads the 16–bit parameter data value for the parameter number
selected.

PLC Block Transfer Instruction Data

BTW instruction length:

3 words

BTR instruction length:

4 words

Message Length

3

Header

Word 1

Header

Word 1

PLC Decimal Length

769

Parameter Number

PLC Decimal Value

769 –– Message OK

Parameter Value or

Status Word

Parameter Number

-31999 –– Message Error

Message Structure

Header

Word 2

Data

Word 3

Header

Word 2

Header

Word 3

Header

Word 4

0

PLC Request –– Block Transfer Write

Drive Response –– Block Transfer Read

Message Operation

The Parameter Value Read function specified in the BTW reads a
parameter value from the drive and places that value (or an error
code) in word 4 of the BTR data file. The value shown is in device
units.

If an error has occurred:

Word 2 of the BTR returns a value of -31999.

Word 4 contains the status code.

Parameter Read

Parameter Value Read