Fault queue, Plc block transfer instruction data, Fault entry read full – Rockwell Automation 1336T PLC Comm. Adapter, Series B, FRN 2.xx-3.xx User Manual

Page 167

Advertising
background image

7–21

Publication 1336 FORCE–5.13 –– September, 1998

The Fault Entry Read Full function reads the contents of the fault
queue entry number specified. A message is returned that includes
the fault text and fault code associated with the specified fault queue
entry and the time stamp associated with the fault.

PLC Block Transfer Instruction Data

BTW instruction length:

3 words

BTR instruction length:

12 or 16 words

Message

3

Header

Word 1

Header

Word 1

PLC Decimal Value

1792

Header

Word 2

Fault Queue Entry

Number

Header

Word 3

PLC Decimal Value

1792 –– Message OK

Header

Word 2

Data

Word 3

-30976 –– Message Error

Data

Word 4

Data

Word 5

Fault Text

Character 2

Character 1

Fault Text

Character 4

Character 3

Fault Queue Entry

Number

Data

Word 6

Fault Text

Character 6

Character 5

Data

Word 7

Fault Text

Character 8

Character 7

Data

Word 8

Fault Text

Character 10

Character 9

Data

Word 9

Fault Text

Character 12

Character 11

Data

Word 10

Fault Text

Character 14

Character 13

Data

Word 11

Fault Text

Character 16

Character 15

Message Structure

0

PLC Request –– Block Transfer Write

Data

Word 12

Fault Code Value

Data

Word 13

Clock Time

Seconds

Ref

Data

Word 14

Clock Time

Hour

Minute

Data

Word 15

Clock Time

Date

Day

Data

Word 16

Clock Time

Year

Month

Drive Response –– Block Transfer Read

Fault Queue

Fault Entry Read Full

Advertising