8–4

Publication 2755-838

Device Dialog

The Device dialog sets the Reader DeviceNet address. Open the
Device dialog by selecting the Device button on the Project dialog or
by double-clicking a Reader name in the project window.

If the Device is online but not in the project

database, the following dialog is displayed:

If the Device is online and in the current project

database, the following dialog is displayed:

Each reader must be assigned a unique DeviceNet address. Shipped
from the factory, the Reader is assigned a default node address of 63.
Assign each Reader an address between 0 and 63.

The DeviceNet Buffer dialog defines the warning provided when the
message buffer reaches 75% capacity. If the buffer capacity is
exceeded, message data will be lost. Access the buffer
configuration dialog by selecting the More button on the Device
Dialog.

When the warning buffer is enabled, you must specify both the
Reader and the output that will be activated.

DeviceNet provides an adjustable background heartbeat that
indicates to a device receiving data that the AdaptaScan is online and
still active. Set the heartbeat pulse period from 0 to 65535
milliseconds (3,000 is the default).