Rockwell Automation 2755 AdaptaScan Software User Manual

Page 151

Advertising
background image

10–14

Publication 2755-838

Flow Control Example

The following shows how DeviceNet Input #8 and Output #16
control the transmission of messages. Output #16 is changed by the
Reader and Input #8 is changed by the controller.

DeviceNet Scan Number

Message Data

DeviceNet

Output #16

DeviceNet

Input #8

1 - Poll

-

OFF (0)

1 - Response

No Message Sent

OFF (0)

2 - Poll

-

ON (1)

2 - Response

Message 1 Sent

ON (1)

3 - Poll

-

OFF (0)

3 - Response

Message 2 Sent

OFF (0)

Note: You can disable handshaking by deselecting the handshake
checkbox (see page 10–11). With handshaking disabled, it may be
possible to miss data if the Reader decodes data too fast for the
controller. In addition, identical data may not be read unless data
that changes such as package count is added to the message sent by
the Reader.