Devicenet addressing – Rockwell Automation 2755 AdaptaScan Software User Manual

Page 135

Advertising
background image

9–14

Publication 2755-838

DeviceNet Addressing

The addressing of the Reader DeviceNet I/O requires 2 bytes. The
following tables show the byte and bit address for each of the inputs
and outputs. Use these charts when setting up the DeviceNet
scanner.

I/O data is addressed and sent to other DeviceNet devices through a
DeviceNet scanner (Catalog No. 1771-SDN or 1747-SDN). To
configure the scanner, you will need to provide the size of the I/O
data, the beginning byte and bit number of the data and the
destination of the I/O data.

Poll Data Structure (DeviceNet Inputs)

Description

Byte #

Bit #

DeviceNet Input #1

0

0

DeviceNet Input #2

0

1

DeviceNet Input #3

0

2

DeviceNet Input #4

0

3

DeviceNet Input #5

0

4

DeviceNet Input #6

0

5

DeviceNet Input #7

0

6

Poll Tx Size = 1 Byte

Response Data Structure (DeviceNet Outputs)

Description

Byte #

Bit #

DeviceNet Output #1

0

0

DeviceNet Output #2

0

1

DeviceNet Output #3

0

2

DeviceNet Output #4

0

3

DeviceNet Output #5

0

4

DeviceNet Output #6

0

5

DeviceNet Output #7

0

6

DeviceNet Output #8

0

7

DeviceNet Output #9

1

0

DeviceNet Output #10

1

1

DeviceNet Output #11

1

2

DeviceNet Output #12

1

3

DeviceNet Output #13

1

4

DeviceNet Output #14

1

5

DeviceNet Output #15

1

6

Poll Rx Size = 2 Bytes

Note: Input #8 and Output #16 control the transmission of bar code
message data using DeviceNet master-slave. Refer to Chapter 10.