Power dissipation – Rockwell Automation 2098-IPD-xxx Ultra5000 Intelligent Positioning Drives Installation Manual User Manual
Page 101
![background image](/manuals/580388/101/background.png)
Publication 2098-IN001E-EN-P — April 2002
Specifications and Dimensions
A-5
Power Dissipation
The maximum power losses Ultra5000 are shown below to help in
sizing an enclosure and any required ventilation. Typical heat losses
can run approximately one-half maximum power losses.
Catalog Number
Maximum Loss (Watts)
2098-IPD-005, 005-DN
48 + dissipative shunt
2098-IPD-010, -010-DN
48 + dissipative shunt
2098-IPD-020, -020-DN
50 + dissipative shunt
2098-IPD-030, -030DN
150 + dissipative shunt
2098-IPD-075, -075DN
300 + dissipative shunt
2098-IPD-150, -150DN
500 + dissipative shunt
2098-IPD-HV030, -030-DN
175 + dissipative shunt
2098-IPD-HV050, -050-DN
175 + dissipative shunt
2098-IPD-HV100, -100-DN
350 + dissipative shunt
2098-IPD-HV150, -150-DN
350 + dissipative shunt
2098-IPD-HV220, -220-DN
600 + dissipative shunt