Rockwell Automation 2098-IPD-xxx Ultra5000 Intelligent Positioning Drives Installation Manual User Manual

Page 148

Advertising
background image

Publication 2098-IN001E-EN-P — April 2002

D-2

Wiring Three Phase Power to a Single Phase Ultra5000

Mandatory Neutral

Connection of Isolation

Transformer

A neutral must be connected (shown in the upper diagram of

Figure

D.1

) when single phase drives are attached to a three phase isolating

transformer secondary. It is not necessary that all three phases be
loaded with drives, but each drive must have its power return via the
neutral connection.

Failure to connect the neutral (shown in the lower diagram of

Figure

D.1

) can result in supply voltage swings at the individual loads (i.e.,

drives). This occurs when the neutral point moves vectorially as a
result of load variations normally experienced by the individual
drives. The supply voltage swing may cause undervoltage and
overvoltage trips on the drives, and the drive can be damaged if the
overvoltage limit is exceeded.

Figure D.1

Mandatory Neutral Connection with Safety Ground of Isolation Transformer

Load 1

Load 2

Load 3

Phase 1

Phase 3

Phase2

Any unbalance in load currents will result in unbalanced voltages which could

exceed the voltage limit of the load.

Safety

Ground

Load 1

Load 2

Load 3

Phase 1

Phase 3

Phase 2

Advertising