Voiding of ce compliance, Attention – Rockwell Automation 2098-IPD-xxx Ultra5000 Intelligent Positioning Drives Installation Manual User Manual

Page 150

Advertising
background image

Publication 2098-IN001E-EN-P — April 2002

D-4

Wiring Three Phase Power to a Single Phase Ultra5000

Figure D.2

Mandatory Neutral Connection of Three Phase Line Filter

Voiding of CE Compliance

The three phase and neutral in line filter applications described above
may not be adequate from an EMC aspect for CE compliance.
Therefore EMC validity and CE marking by Rockwell Automation is
voided when three phase and neutral in line filters are used.

N

1

2

3

N

1

2

3

N

1

2

3

N

1

2

3

Load 1

Load 2

Load 3

EMC

Filter

Phase 3

Phase1

Three phase EMC filter feeding multiple single phase loads

A three phase and neutral filter is required

Safety

Ground

Load 1

Load 2

Load 3

Phase 2

3 Phase

Supply

Safety

Ground

EMC

Filter

ATTENTION

!

The three phase isolation transformer and neutral in
line filter applications described in this document
have not been tested for EMC by Rockwell
Automation, and products used in such installations
are not considered CE marked by Rockwell
Automation..

If this three phase isolation transformer and neutral
in line filter application is used, the responsibility for
EMC validation lies with the user and CE marking of
the system becomes the user's responsibility.

If CE compliance is a customer requirement, single
phase line filters which have been tested by
Rockwell and specified for the product should be
used. Refer to AC Line Filters on page C-3.