Digital Inputs

There are sixteen general purpose digital inputs. They are not
connected in hardware to perform a particular function. All digital
inputs have the same hardware configuration, shown in

Figure 2.8

.

Inputs 1 and 2 use high-speed circuitry, with minimal propagation
delays, suitable for use in registration applications. Any input can be
assigned through firmware to latch the motor or auxiliary position in
hardware.

Figure 2.8

Digital Input Circuit

The following table provides a description of the digital input
specifications.

IMPORTANT

Configure your digital inputs, in a group, as active
high (current sinking) or active low (current
sourcing).

Parameter

Description

Minimum

Maximum

ON State Voltage,

Active High
Configuration

Voltage applied to the input, with
respect to IOCOM, to guarantee an ON
state.

10.8V

26.4V

ON State Voltage,

Active Low
Configuration

Voltage applied to the input, with
respect to IOPWR, to guarantee an ON
state.

-26.4V

-10.8V

ON State Current

Current flow to guarantee an ON State

3.0 mA

12.0 mA

OFF State Voltage,

Active High
Configuration

Voltage applied to the input, with
respect to IOCOM, to guarantee an OFF
state.

-1.0V

3.0V