Led as shown in, Figure 4.1 – Rockwell Automation 2098-IPD-xxx Ultra5000 Intelligent Positioning Drives Installation Manual User Manual

Page 84

Advertising
background image

Publication 2098-IN001E-EN-P — April 2002

4-4

Commissioning Your Ultra5000

Figure 4.1

Logic Power and Status LED Display

4. Observe the front panel seven segment Status LED display as

shown in

Figure 4.1

.

If the Logic Power LED is:

Then:

ON

Go to

step 4

.

Not ON

Check your input power connections.
Repeat

step 3

.

Status

PWR

If the Status LED display on your: Is:

Then:

2098-IPD-xxx,
2098-IPD-HVxxx,
2098-IPD-xxx-DN, and
2098-IPD-HVxxx-DN
(all Ultra5000 drives)

Actively cycling segments in
a full circle

The drive is ready. Go to

Configuring

Your Ultra5000

on

Page 4-5

.

2098-IPD-xxx,
2098-IPD-HVxxx,
2098-IPD-xxx-DN, and
2098-IPD-HVxxx-DN
(all Ultra5000 drives)

Actively cycle in a half circle

with address switches set to
MSD=9 and LSD=9

Go to

Understanding Communication

Switch Settings

on

Page 4-2

and reset

your address switches according to the
table.

2098-IPD-xxx,
2098-IPD-HVxxx,
2098-IPD-xxx-DN, and
2098-IPD-HVxxx-DN
(all Ultra5000 drives)

Actively cycle in a half circle

with address switches set
according to the table in

Understanding
Communication Switch
Settings

on

Page 4-2

.

Your firmware requires an upgrade. Go
to

Configuring Your Ultra5000

on

Page 4-5

.

2098-IPD-xxx,
2098-IPD-HVxxx,
2098-IPD-xxx-DN, and
2098-IPD-HVxxx-DN
(all Ultra5000 drives)

Flashing an “E” followed by
two numbers

Go to the chapter

Maintaining Your

Ultra5000

beginning on

Page 5-1

.