Installing Your Ultra5000

1-11

Bonding Multiple Subpanels

Bonding multiple subpanels creates a common low impedance exit
path for the high frequency energy inside the cabinet. Subpanels that
are not bonded together may not share a common low impedance
path. This difference in impedance may affect networks and other
devices that span multiple panels. Refer to the figure below for
recommended bonding practices.

Figure 1.4

Multiple Subpanels and Cabinet

Recommended:
Bond the top and bottom of each subpanel to the cabinet

using 25.4 mm (1.0 in.) by 6.35 mm (0.25 in.) wire braid.

Scrape the paint around each fastener
to maximize metal to metal contact.

Bonded cabinet

ground bus to

subpanel

Recommended:
Bond the top and bottom of each subpanel to the cabinet

using 25.4 mm (1.0 in.) by 6.35 mm (0.25 in.) wire braid.

Scrape the paint around each fastener
to maximize metal to metal contact.

Bonded cabinet

ground bus to

subpanel