Understanding ultra5000 i/o specifications, Digital i/o power supply, Understanding ultra5000 i/o specifications -19 – Rockwell Automation 2098-IPD-xxx Ultra5000 Intelligent Positioning Drives Installation Manual User Manual

Page 45: Digital i/o power supply -19

Advertising
background image

Publication 2098-IN001E-EN-P — April 2002

Ultra5000 Connector Information

2-19

Understanding Ultra5000

I/O Specifications

A description of the Ultra5000 input/output is provided on the
following pages.

Digital I/O Power Supply

Power for the digital I/O on 0.5 kW, 1.0 kW, and 2.0 kW Ultra5000
230V drives (2098-IPD-005 through -020) and all 460V drives
(2098-IPD-HVxxx-xx) must be provided by an external 12-24V dc
power supply.

Power for the digital I/O on 3.0 kW through 15 kW Ultra5000 drives
(2098-IPD-030 through -150) is provided by an external 12-24V dc
power supply or by a 24V dc power source internal to the drive.

Two jumpers on the regulator board must be repositioned if the
internal power source is to be used. Refer to

Figure 3.2

on

Page 3-3

for the location of the jumpers. The internal supply is fused by F1, a
fast acting 1A fuse. The common for the internal supply is lightly
referenced to ground, through a 1M ohm resistor. When using the
internal 24V supply, the common must be grounded during
installation to meet the European Low Voltage Directive.

The following table provides a description of the requirements for an
external digital I/O power supply for all Ultra5000 drives
(2098-IPD-005-xx through 2098-IPD-150-xx, and 2098-IPD-HV030-xx
through 2098-IPD-HV220-xx).

The following table provides specifications on the internal digital I/O
power supply for the 230V Ultra5000 3.0 kW through 15 kW drives
(2098-IPD-030 through -150 only).

Parameter

Description

Minimum Maximum

I/O Power Supply
Voltage

Voltage range of the external power supply
for proper operation of the digital I/O.

10.8V 26.4V

I/O Power Supply
Current

Current draw from the external power
supply for the digital I/O, not including the
relay output usage.

— 300

mA

Parameter

Description

Minimum Maximum

Output Voltage

Voltage difference between I/O PWR and
I/O COM

21.6V

28.0V

Output Current

Current flow

300 mA

Advertising