Maintaining Your Ultra5000

5-5

21

Auxiliary Encoder state error

The auxiliary encoder encountered an
illegal transition.

• Use shielded cables with twisted

pair wires.

• Route the encoder cable away from

potential noise sources.

• Bad encoder - replace encoder.

• Check the ground connections.

22

Motor Thermal Protection Fault

The internal filter protecting the motor
from overheating has tripped.

• Reduce acceleration rates.

• Reduce duty cycle (ON/OFF) of

commanded motion.

• Increase time permitted for motion.

• Use larger Ultra5000 and motor.

• Check tuning.

23

IPM Thermal Protection Fault

The internal filter protecting the drive
from over heating has tripped.

• Reduce acceleration rates.

• Reduce duty cycle (ON/OFF) of

commanded motion.

• Increase time permitted for motion.

• Use larger Ultra5000 and motor.

• Check tuning.

24

Excess Velocity Error

Velocity error limit was exceeded.

• Increase time or size of allowable

error.

• Reduce acceleration.

• Check tuning.

25

Reserved

Call your local Allen-Bradley
representative.

26

User-Specified Velocity Fault

User specified velocity level was
exceeded.

Increase to a less restrictive setting.

27 - 28

Reserved

Call your local Allen-Bradley
representative.

29

Encoder Output Frequency Exceeded

Encoder output frequency exceeds the
maximum user specified value. This
only applies when the encoder output
mode is software.

• Increase the Output Encoder Limit

parameter.

• Increase the encoder output divider

parameter.

30 - 33

Reserved

Call your local Allen-Bradley
representative.

34

Ground Fault

Wiring error.

Check motor power wiring.

Motor internal ground short.

Replace motor.

Internal malfunction.

Disconnect motor power cable from
drive and enable drive with current
limit set to 0. If fault remains, call your
A-B representative. If fault clears, then
a wiring error or motor internal
problem exists.

35

Precharge Fault

Low AC input voltage.

Check input AC voltage on all phases.

36

Power Circuitry Overtemperature

Excessive heat exists in the power
circuitry.

• Reduce acceleration rates.

• Reduce duty cycle (ON/OFF) of

commanded motion.

• Increase time permitted for motion.

• Use larger Ultra5000 and motor.

• Check tuning.

Error

Code

Problem or Symptom

Possible Cause(s)

Action/Solution