Figure – Rockwell Automation 2098-IPD-xxx Ultra5000 Intelligent Positioning Drives Installation Manual User Manual

Page 22

Advertising
background image

Publication 2098-IN001E-EN-P — April 2002

1-8

Installing Your Ultra5000

Figure 1.2

Transformer Sizing Based on Speed/Torque Data for Single Phase System

The formula and calculation are:

Definitions:
kW = power or real power
KVA = apparent power
Transformer KVA rating = (Sum of average output power of each axis) x 2.0.

IMPORTANT

Calculations are multiplied by a factor to compensate
for the power and loss elements within a power
system.

•A factor of 2.0 is used with a single phase system.
•A factor of 1.5 is used with a three phase system.

This factor minimizes the effects of the secondary
line voltage sagging in the transformer during peak
current periods.

IMPORTANT

If you are using the Rockwell Automation/
Allen-Bradley system sizing program, the average
speed and average torque data has already been
calculated and can be used in the equation. If you
are not sure of the exact speed and torque in your
application, another approach is to look at the
speed/torque curve for your Ultra5000/motor
combination and use the values for the worst case
continuous speed and torque.

TORQUE (lb-in)

3200 rpm

SPEED (RPM)

23.0 lb-in

Application

Operating Point

KVA

Speed RPM

(

) Torque lb in

(

)

×

63 025

,

--------------------------------------------------------------------------------

746Watts

HP

------------------------

×

KVA

1000Watts

---------------------------

Ч

2.0

Ч

=

KVA

3200rpm

23.0lb

in

×

42 250

,

-------------------------------------------------------

=

TransformerSize

1.75KVA

=

Advertising