Publication 2098-IN001E-EN-P — April 2002

Ultra5000 Connector Information

2-27

Hall Inputs

The Ultra5000 uses Hall Signals to initialize the commutation angle for
sinusoidal commutation. Hall Signals must be single-ended and can be
either open collector type or TTL type.

Figure 2.14

shows the

configuration of the Hall inputs. If the motor does not have Hall
signals, the drive can configured through software to omit the Hall
signal requirement.

Figure 2.14

Hall Input Configuration

Thermostat Input

The Ultra5000 can monitor a thermostat signal from a motor and will
generate a fault if the motor overheats.

Figure 2.15

shows the

configuration of the thermostat input.

Figure 2.16

on page

2-28

shows

a typical connection to a motor with a normally closed thermostat.
The logic is designed so that an open condition will generate a fault. If
the motor does not have a thermostat signal, the drive can be
configured through software to ignore the signal.

Figure 2.15

Thermostat Input Configuration

1k

1k

+ 5 V

+ 5 V

56

µF

COMMON

COMMON

S1, S2, or S3

1k

1k

+ 5 V

+ 5 V

0.01

µF

COMMON

COMMON

TS