Publication 2098-IN001E-EN-P — April 2002

Interconnect Diagrams

B-21

Figure B.19

Emergency Stop Contactor Wiring

1

Exposed power wiring conductors that are not shielded are a source of RFI noise. Keep exposed conductors as
short as possible and isolated from sensitive devices and wiring.

2

The safety ground (GND) and shield connections are permanently connected. This is essential for electrical
safety

.

3

Unbraid all cable shields and bond together, connecting directly to the grounded terminal or stud. Do not use the
shield drain wire for this bonded connection.

IMPORTANT

The safety ground is not connected to local ground
at the point where the contactor is inserted in the
lines, but the shield is. This is done for EMC reasons.

1

1

1

1

1

1

3

2

Isolated terminal

Enclosure wall

Grounded terminal or stud

Unbraided shield

Contactors

Drive

Motor

Resistors

W

V

U

W

V

U

Gnd

Gnd