Ventilation Requirements

This section provides information to assist you in sizing your cabinet
and locating your Ultra5000 drive(s) inside the cabinet.

Figure 1.1

Minimum Clearance Requirements

Refer to Power Dissipation on page A-5

for Ultra5000 power

dissipation specifications.

50.8 mm (2.0 in.) clearance

for airflow and installation

50.8 mm (2.0 in.) clearance

for airflow and installation

Allow 12.7 mm (0.5 in.)

side clearance

Allow 12.7 mm (0.5 in.)

side clearance

Motor cable entry area for ground

clamp

Minimum cabinet depth = 243.8 mm (9.6 in.)

Minimum front clearance = 76.2 mm (3.0 in.)

IMPORTANT

If the cabinet is ventilated, use filtered or
conditioned air to prevent the accumulation of dust
and dirt on electronic components. The air should be
free of oil, corrosives, or electrically conductive
contaminates.