Ventilation requirements, Ventilation requirements -6, Figure 1.1 – Rockwell Automation 2098-IPD-xxx Ultra5000 Intelligent Positioning Drives Installation Manual User Manual
Page 20
Publication 2098-IN001E-EN-P — April 2002
1-6
Installing Your Ultra5000
Ventilation Requirements
This section provides information to assist you in sizing your cabinet
and locating your Ultra5000 drive(s) inside the cabinet.
Figure 1.1
Minimum Clearance Requirements
Refer to Power Dissipation on page A-5
for Ultra5000 power
dissipation specifications.
50.8 mm (2.0 in.) clearance
for airflow and installation
50.8 mm (2.0 in.) clearance
for airflow and installation
Allow 12.7 mm (0.5 in.)
side clearance
Allow 12.7 mm (0.5 in.)
side clearance
Motor cable entry area for ground
clamp
Minimum cabinet depth = 243.8 mm (9.6 in.)
Minimum front clearance = 76.2 mm (3.0 in.)
IMPORTANT
If the cabinet is ventilated, use filtered or
conditioned air to prevent the accumulation of dust
and dirt on electronic components. The air should be
free of oil, corrosives, or electrically conductive
contaminates.