Devicenet network status led, Devicenet network status led -7 – Rockwell Automation 2098-IPD-xxx Ultra5000 Intelligent Positioning Drives Installation Manual User Manual

Page 93

Advertising
background image

Publication 2098-IN001E-EN-P — April 2002

Maintaining Your Ultra5000

5-7

DeviceNet Network Status LED

Use the table below for troubleshooting the DeviceNet Network Status
LED on your Ultra5000 (2098-IPD-xxx-DN, or -HVxxx-DN).

If the Network

Status LED is:

Status is:

Potential Cause is: Possible Resolution is:

Off

• Not powered
• Not on-line

• No power going to

the device

• Failed Duplicate

MAC ID check

1. Check the Module Status LED to verify that the drive is powered.
2. Check that one or more nodes are communicating on the network.
3. Check that at least one other node on the network is operational and the

data rate is the same as the drive.

Flashing-green

• On-line
• Not

connected

• Passed Duplicate

MAC ID check

• No connection

established

No action is needed. The LED is flashing to signify that there are no open
communication connections between the drive and any other device. Any
connection (I/O or explicit message) made to the drive over DeviceNet will
cause the LED to stop flashing and remain Steady-ON for the duration of any
open connection.

Steady-green

• On-line
• Connected

One or more
connections
established

No action needed. This condition is normal.

Flashing-red

• On-line
• Time-out

I/O connection timed
out

1. Re-initiate I/O messaging by the master controller.
2. Reduce traffic or errors on the network so that messages can get through

within the necessary time frame.

Steady-red

Network Failure

• Failed Duplicate

MAC ID check

• Bus-off

1. Ensure that all nodes have unique addresses.

2. If all node addresses are unique, examine network for correct media

installation.

3. Ensure that all nodes have the same Data Rate.

Advertising