Publication 2098-IN001E-EN-P — April 2002

B-24

Interconnect Diagrams

900 Watt Passive Shunt Module

Use the 2090-UCSR-P900 passive shunt module with the Ultra5000
drives (2098-IPD-075-xx or 2098-IPD-150-xx).

Use shielded, high temperature 75° C (167° F), 600V, 10 mm

2

(8

AWG), 3.05 m (10 ft) maximum, copper wire. Follow one of the
methods given below to reduce the effects of EMI noise:

• Install wires using twisted pairs (two turns per foot minimum), as

shown in the figure above. Keep unshielded wires as short as
possible.

• Use shielded, twisted cable (ground shield at shunt and drive).

• Use shielded metal conduit (ground conduit at shunt and drive).

For more information, refer to the

900 Watt Passive Shunt Module

Installation Instructions

, publication

2090-IN001

.

2090 Passive Shunt Module

A 2090-SRxxx-xx passive shunt module can be used with 460V
Ultra5000 drives (2098-IPD-HV030-xx, -HV050-xx, -HV100-xx,
-HV150-xx, and -HV220-xx) operating with 460V or 230V input
power.

Note: Fusing on the 2090-SRxxx-xx passive shunt module must be

changed to accommodate 230V input power.

Use shielded, high temperature 105

°

C (221

°

F), 600V, 6 mm

2

(10

AWG), 3.05 m (10 ft) maximum, braided copper wire to connect
between the drive’s TB2-1 and TB2-3 external shunt terminals and the
shunt module terminals. Follow one of the methods below to reduce
the effects of EMI noise:

• Install wires using twisted pairs (two turns per foot minimum).

Keep unshielded wires as short as possible.

• Use shielded, twisted cable (ground shield at shunt and drive).

• Use shielded metal conduit (ground conduit at shunt and drive).

For more information, refer to the

2090 Series Passive Shunts

Installation Instructions

, publication

2090-IN004

.