Publication 2098-IN001E-EN-P — April 2002

Installing Your Ultra5000

1-5

Minimum Mounting Requirements

There are several things that you need to take into account when
preparing to mount the Ultra5000:

• The Ultra5000 is classified as IEC controlgear, and must be housed

in an enclosure that meets IEC60529 requirements for electrical
enclosure of controlgear.

• The ambient temperature of the location in which you will install

the Ultra5000 must not exceed 55° C (131° F).

• You must install the enclosure on a flat, rigid, vertical surface that

will not be subjected to shock, vibration, moisture, oil mist, dust, or
corrosive vapors.

• You need to maintain minimum clearances (refer to

Figure 1.1

)

within the enclosure for proper airflow, easy module access, and
proper cable bend radius.

Refer to

Appendix A

for mounting dimensions, power dissipation, and

environmental specifications for the Ultra5000.