4

Set up Your System Architecture

103

5. Click Next to review the selections, then click Finish.

For controller types CompactLogix and ControlLogix, the output file will have
the file name you specified with a .L5K extension and a controller type of 1756-
L63. L5K files are complete ladder files rather than library files.

For controller type of MicroLogix or SLC 500, the ADR wizard creates a set of
output files: <filename>.SLC, .SY5 and .SY6 for import into a controller you
create in RSLogix 500 software.

For controller type of PLC-5, the ADR wizard creates the output file
<filename>.PC5 for import into a controller you create in RSLogix 5 software.

Import the Wizard Output File into the Controller Logic Program

The final step is to open the applicable RSLogix software and import the library file
created by the ADR Wizard into the controller logic program. Refer to the RSLogix
documentation and online Help for additional information. You may need to change the
controller type and correct items such as data table values or I/O configuration, in
response to errors and warnings. Minor errors and warnings frequently occur as part of the
library import process and cannot be avoided.

The ADR Wizard does not attempt to determine if its output file will fit into the controller
memory. This check is made within the RSLogix software when the import is made.

If adding ADR to an existing CompactLogix and ControlLogix
controller, the ADR Wizard output file will need to be opened in
a separate instance of RSLogix 5000 software and the logic and
tags copied and pasted into the existing program.