Evaluation type. Magnitude (analog) or state (discrete).
Threshold. This is the value at which to trigger a setpoint action.
Hysteresis. This is the dead-band around the threshold.
Assert Delay. This is the amount of time to wait before triggering a setpoint action
after satisfying the setpoint test condition.
De-assert Delay. This is the amount of time to wait before releasing a setpoint
action after a setpoint condition is no longer satisfied.
Setpoint Outputs Tab
This relates setpoints to output actions for the 1426 PowerMonitor 5000 unit.
Input source
Setpoints 1…20
Input can also be a Logic Gate, and the Logic Gate is then defined in the Setpoint
Output Logic Gate dialog box.
Output action
Select actions from the drop down list.
Setpoint Output Logic Gate Dialog Box
This dialog box defines the output action related to a setpoint output logic gate for the
1426 PowerMonitor 5000 unit.
Input source
Between tow and four setpoints can be defined as inputs.
Logic Gate
Logical functions can be one of the following: AND, NAND, OR, NOR, XOR,
XNOR.
Each defined input setpoint can be inverted.