Rockwell Automation 9307 FactoryTalk EnergyMetrix User Manual

Page 310

Advertising
background image

FactoryTalk EnergyMetrix Software

310

Error Codes

Error codes listed in the System Status or Device Status detail screens are passed through
from RSLinx Classic. The most common error codes are listed here.

Error Code:  1

Error Description: Driver name is invalid

Detailed Description: This error can usually be corrected simply by opening RSWho in
RSLinx and verifying the device is communicating (that is, there is no red X through the
device).

Error Code:  27

Error Description: I/O operation not attempted

Detailed Description: Can be caused by configuring the device as on ‘Ethernet’ but the
device is actually EtherNet/IP (or vice versa) or by the device's Remote I/O rack/group
address not being in the processor's scan list, if it is a Remote I/O device.

Error Code:  158

Error Description: Driver name is invalid

Detailed Description: The RSLinx driver name is incorrect or the driver is not configured
in RSLinx.

Error Code:  261 or 261024

Error Description: Application layer timed out waiting for a response

Detailed Description: This is a timeout error indicating a physical problem with the link
between RSLinx and the device or a problem with the device itself. Check cabling and the
health of the device (is it faulted, etc).

Error Code:  272

Error Description: Illegal command or format, including an odd address

Detailed Description: This is typically caused by a bad tag address. Check that the tag
address is correct. If the tag is located in a ControlLogix processor verify that the PLC
mapped file is present and is the correct file number and the tag is mapped to that file
number.

Advertising