5

Visualize Energy Usage

147

To set up a new alarm, navigate to the selected Meter Setup page and click the Add a new
alarm link at the bottom of the page.

The Alarm Setup page appears.

Setup Parameters

Alarm Information

Enabled checkbox - click to enable or disable alarm.

Alarm Name - alphanumeric name for the alarm, displayed in the Active Alarms and
Alarm Summary pages.

Meter Tag - select the meter tag to evaluate for alarm condition.

Alarm severity - select from the pull-down menu, displayed in the Active Alarms and
Alarm Summary pages.

Message - Message to be displayed in the Active Alarms and Alarm Summary pages
and also in alarm-triggered email messages.

‘Send email on’ checkboxes - select one or both to send an email when desired.

For emails to be sent on alarm, a smtp server must be configured
for the server, alarm notifications enabled and alarm
subscriptions set up for the applicable users.