Rockwell Automation 9307 FactoryTalk EnergyMetrix User Manual

Page 170

Advertising
background image

FactoryTalk EnergyMetrix Software

170

Download Button

This downloads configuration settings from the database to the power monitor. After
downloading, click OK to save the configuration and close the Device Configuration
window.

Voltage/Current Tab

This displays and sets operating parameters, including wiring mode, and current and
voltage scaling (PT and CT ratios), for an Allen-Bradley PowerMonitor 5000 unit.

Metering mode option

From the list, select the mode that represents the power monitor wiring configuration.
An incorrect setting will cause the power monitor to calculate incorrect values.

Real time update rate option

This controls how fast the power monitor updates measured values and how many
cycles are averaged to provide results with less variation.

Nominal system frequency option

Select 50 or 60 Hz

Voltage PT and VN PT option

Primary. Enter the first value from 1…10,000,000 for the PT (potential
transformer) ratio (XXX:XXX), indicating the voltage rating at the high end of
the transformer.

Secondary. Enter the second value from 1 to 600 for the PT ratio (XXX:XXX),
indicating the voltage rating at the low end of the transformer. This value also
determines whether the master module uses high or low voltage input signals.

Current CT and Neutral Current I4 CT

Primary. Enter the first value from 1…10,000,000 for the CT (current
transformer) ratio (XXX:XXX), indicating the current rating at the high end of the
transformer.

Secondary. Enter the second value from 1…5 for the CT ratio (XXX:XXX),
indicating the current rating at the low end of the transformer.

Nominal system voltage

Enter a value that represents the nominal voltage of the system. This parameter is used
in the metering functions and in conjunction with voltage sag and swell functions.