Rockwell Automation 9307 FactoryTalk EnergyMetrix User Manual

Page 158

Advertising
background image

FactoryTalk EnergyMetrix Software

158

Setpoint Output Status

This displays setpoint output configuration and stats from an Allen-Bradley 1426
PowerMonitor 5000 unit.

Input Source - The input source to trigger the output

Output Action - The action for the output

Status - The current value for the Output - True or False

Waveform Tab

This displays captured oscillographs from an Allen-Bradley 1426 PowerMonitor 5000
M6 or M8. Oscillography features include:

Simultaneous capture of all eight (8) voltage and current channels.

Up to 61/4 kHz sampling rate (1024 samples/cycle at 50 or 60 Hz). Captures
include up to the 63rd (M6) or 127th (M8) harmonic.

Up to 256 waveform files or 21,600 cycles of waveform data are stored in
non-volatile memory.

Each capture may contain up to 3600 cycles of data per channel plus the pre- and
post-event cycles as configured.

Waveform data is comprised of cycle-by-cycle FFT data and is stored in
compressed format.

Configurable pre- and post-event cycles (up to 15 cycles pre and 30 cycles post)
allows capture of data surrounding the triggering event.

Waveform capture is triggered in three ways:

Manually, through a command;

Automatically by the power monitor when it detects a sag or swell event; and

In response to a waveform synchronization broadcast message.

When a capture is displayed, a vertical dashed red link marks the trigger position.

Advertising