7

RT (Real Time)

175

Save status changes to event log

Select this check box to write input activity to the event log. Clear the check box to
NOT record input activity.

DST Tab

PowerMonitor 5000 units can be configured to automatically adjust for daylight savings
time. DST is disabled by default.

Enable Daylight Saving Time

Enables the daylight saving time function. Range 0 = disable, 1 = enable

When Daylight Saving Time Starts

Start hour
Selects the hour of the day when DST begins. Range 0 = midnight, 1 = 1:00 a.m.,
…, 23 = 11:00 p.m.

Start day instance
Selects which instance of the DST start day in the DST start month when DST
begins. Range 1 = first, 2 = second, 3 = third, 4 = fourth, 5 = last

Start day
Selects the day of the week when daylight savings time begins. Range 0 = Sunday,
1 = Monday, …, 7 = Saturday

Start month
Selects the calendar month when daylight savings time begins. Range 1 = January,
2 = February, …, 12 = December

When Daylight Saving Time Ends