Rockwell Automation 9307 FactoryTalk EnergyMetrix User Manual

Page 65

Advertising
background image

4

Set up Your System Architecture

65

Device Information

Enable Check Boxes

The enable check boxes appear in both view and edit modes. In edit mode they can be
clicked and unclicked. In view mode they are grayed out.

Enable Device - Turns on and off communication between FactoryTalk EnergyMetrix
and the device. A device must be enabled for any of the other enables to be effective.

Enable Real-time Logging - Turns on and off logging of meter tags in meters attached
to the device. Does not appear on setup page for roll-up servers. More info...

Enable Auto Data Repopulation - Turns on and off ADR. Supported in only certain
devices such as Allen-Bradley power monitors and MicroLogix EEMs. Does not
appear on device setup screen for OPC devices. See

Automatic Data Repopulation on

page 98

.

Enable PQ Events Logging - Turns on and off power quality event logging. Applies
only to Allen-Bradley Powermonitor 3000 model M6 and M8 devices.

Device Identification

These parameters establish some general and some device-class specific details.

Parent Group - Applies to all devices. Specifies the group or domain the device to
which the device is assigned. A device can only be assigned to one group or domain.

Device Class - Applies to all devices. A device class is a set of properties that informs
FactoryTalk EnergyMetrix how to interact with the device.