FactoryTalk EnergyMetrix Software

172

Load factor log auto reset/clear day

Automatically stores the current peak, average and load factor results as a record in
the non-volatile load factor log and clears the peak and average demand values at the
end of the specified day of each month.

If this parameter is set to 29…31 and the month does not contain that many days, the
record will be saved on the last day of that month. The parameter can also be set to
Disable.

Setpoints Tab

This establishes setpoint parameters for the 1426 PowerMonitor 5000 unit. The power
monitor uses setpoints to generate alarms and control relays based on metering parameter
values.

Setpoint Parameters

A setpoint is a group of seven parameters. To edit a setpoint, select it in the list and
double-click the box containing the arrow indicator.

Parameter. This identifies which parameter to monitor.

Test Condition. Defines how the parameter is evaluated: Greater than, less than,
or equal to.

Allen-Bradley power monitors are NOT intended to function as protective relay
devices.