DeviceNet Adapter for use with DPI AC Drives

Amount of time that a scanner will wait to check for data in the
adapter.

When COS (change of state) data exchange has been set up, this is
the maximum amount of time between scans. Scans will happen
sooner if data changes.

When cyclic data exchange has been set up, this interval is the fixed
time between scans. This interval is configured in the scanner.

Destination in the drive of the Peer Input. The adapter receives this
data from the network and sends it to the drive.

Important: These parameters can be changed only when Peer Inp

Enable (37) is Off.

Important: If a 32-bit Datalink or Reference is used in Peer A Input

(30), Peer B Input (31) cannot be used.

29

COS/Cyc Interval

Range:

0 to 655.35 seconds

Default:

0 seconds

Type:

Read Only

Reset Required: N/A

30
31

Peer A Input
Peer B Input

Range:

0 = Off
1 = Cmd/Ref
2 = DL A Input
3 = DL B Input
4 = DL C Input
5 = DL D Input

Default:

0 = Off

Type:

Read/Write

Reset Required: No